540MW AI Data Center - Div 26 Switchgear & UPS Package · PRE-BID QUOTE CHECK

540MW AI Data Center - Div 26 Switchgear & UPS Package

Div 26 Master Spec.pdfvs.Switchgear Quote.pdf
Overall Spec Compliance
55% Match
2 Critical Deviations Found
Est. Financial Risk Exposure
$68,500
Potential Change-Order Risk
Spec Section & ParameterMaster Spec RequirementVendor Submittal / Quote ValueStatusCost Impact / Risk Note
26 24 13
Short-Circuit Withstand Rating
[PAGE 42] Para 2.04.B
100kA RMS symmetrical; arc-resistant Type 2B
[PAGE 14] BOM 4
65kA standard enclosure
CRITICAL EXCLUSION / NON-COMPLIANT
$38,500
Bus bracing and arc-resistant upgrade; potential 14-week lead impact.
26 13 26
Enclosure Rating
[PAGE 18] Para 2.02.A
NEMA 1A gasketed, UL 1558
[PAGE 6] 3.1
NEMA 1A gasketed, UL 1558
COMPLIANT
—
Matches specification.
26 33 53
IEEE 519 THD Harmonic Limits
[PAGE 61] 2.08.C
THDi <= 5% at full load
[PAGE 22] Datasheet
THDi < 8%; 6-pulse rectifier
DEVIATION / RISK
$12,000
Active harmonic filter or 12-pulse option needed.
26 33 53
UPS Module Redundancy
[PAGE 58] 2.06.A
N+1; 1500kVA per block
[PAGE 19] BOM 11
4 x 500kVA N+1 modules
COMPLIANT
—
N+1 configuration satisfies capacity.
26 09 13
SCADA / Modbus / BACnet Points
[PAGE 77] 2.11.D
Modbus TCP + BACnet/IP; 240 EPMS points
[PAGE 31] Comms
Modbus RTU only; points by others
CRITICAL EXCLUSION / NON-COMPLIANT
$9,500
Gateway and integration labor excluded.
26 13 26
Main Bus Ampacity
[PAGE 20] 2.03.A
3000A copper; silver-plated joints
[PAGE 7] BOM 1
3000A copper; tin-plated joints
DEVIATION / RISK
$4,200
Confirm EOR acceptance or upgrade plating.
26 24 13
Voltage Class / BIL
[PAGE 40] 2.01.B
15kV class; 95kV BIL
[PAGE 12] Ratings
15kV class; 95kV BIL
COMPLIANT
—
Matches specification.
26 05 73
Arc Flash Study & Labels
[PAGE 88] 3.04.A
Vendor IEEE 1584-2018 study and labels
[PAGE 33] Exclusions
Not referenced
AMBIGUOUS / RFI NEEDED
$4,300
Clarify study scope owner.
26 01 26
Factory Witness Testing
[PAGE 92] 3.07.B
Owner-witness FAT; two trips included
[PAGE 34] Clarifications
Standard FAT; witness travel excluded
DEVIATION / RISK
—
Travel costs may shift to subcontractor.
26 13 26
Seismic Certification
[PAGE 24] 2.05.A
IBC 2021 / OSHPD; SDS 1.5g
[PAGE 9] Certs
IBC 2021; SDS 1.5g certified
COMPLIANT
—
Certification attached.